Product Description
1000VA (1KVA) On-Line Rackmount UPS 800W
Technical Specification
Capacity
1000 VA / 800 W
Input
Voltage
100/110/115/120/127 VAC or 200/208/220/230/240 VAC
Voltage Range
55-150 VAC or 110-300 VAC @ 50% load, 85-140 VAC or 160-280 VAC @ 100% load
Frequency Range
40 Hz ~ 70 Hz
Power Factor
≥ 0.99 @ nominal voltage (100% load)
Output
Output Voltage
100/110/115/120/127 VAC or 200/208/220/230/240 VAC
AC Voltage Regulation (Batt. Mode)
±1%
Frequency Range (Synchronized Range)
47~53 Hz or 57~63 Hz
Frequency Range (Batt. Mode)
50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz
Current Crest Ratio
3:1 (max.)
Harmonic Distortion
≤ 3 % THD (Linear Load) ; ≤ 6 % THD (Non-linear Load)
Transfer Time
AC Mode to Batt. Mode
Zero
Inverter to Bypass
4 ms (Typical)
Waveform (Batt. Mode)
Pure Sinewave
Efficiency
AC Mode
88 %
Battery Mode
83%
Battery
Standard Model
Battery Type
12 V / 9 Ah
Numbers
2
Typical Recharge Time
4 hours recover to 90% capacity
Charging Current (max.)
1 A
Charging Voltage
27.4 VDC ± 1%
Long-run Model
Battery Type
Depending on the applications running
Numbers
2 3
Charging Current (max.)
1A/2A/4A/6A (Adjustable)
Charging Voltage
27.4 VDC ± 1% 41.0 VDC ± 1%
Indicators
LCD Display
UPS Status, Load Level, Battery Level, Input/Output Voltage, Discharge timer and Fault conditions
Alarm
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding every twice second
Fault
Continuously Sounding
Physical
Standard Model
Dimensions, D X W X H(mm)
310 x 438 x 88[2U]
Net Weight (kgs)
12
Long-run Model
Dimensions, D X W X H(mm)
310 x 438 x 88[2U]
Net Weight (kgs)
9
Environment
Humidity
20-90 % RH @ 0- 40° (non-condensing)
Noise Level
Less than 50dB @ 1 meter
Management
Smart RS-232 and USB
Supports Windows® 2000/2003/XP/Vista/2008. Windows® 7/8, Linus and MAC
Optional SNMP
Power management from SNMP manager and web browser